Providing multifunctional ventilation, MEGAPHOENIX discharges hot air with a double door system that works independently of each other. Pneumatic or electric side flaps provide ventilation even in rainy weather. The top flaps are controlled by remote-controlled pneumatic pistons or electric motors.
In the event of a fire, the smoke and heat evacuation doors open automatically and manually by a heat-sensitive mechanism placed under the upper wings or by receiving a signal from the building automation to evacuate smoke and heat.
Aerodynomically shaped top and inner covers are equipped with rubber seals for insulation. MEGAPHOENIX can be manufactured in a wide range of sizes up to 1,900 x 3,000 mm.
| MATERIAL PROPERTIES | ||
|---|---|---|
| FRAMEWORK | UPSTAND | SURFACE |
| AlMg3 Unpainted (std.) RAL Painting (ops.) | 1.2 mm GALVANIZED SHEET (ops.) | 16/5 multi-wall PC (std.) A1/A2/Aero (ops.) |
| EN 12101-2 | |||||
|---|---|---|---|---|---|
| Aa | Snow Load | Wind Load | Temperature Resistance | Mechanical Strength | Outdoor Environment |
| 0,65 | SL 500 (pnm/T=-15) SL 750 (pnm,24v/T=0) | WL 1500 | B 300 | Re 1.000 + 10.000 | T= -15 (pnm) T= 0 (24v) |
| SIZE RANGE | ACCESSORIES | Ventilation | ||||||
|---|---|---|---|---|---|---|---|---|
| MİN (mm) | MAKS (mm) | Windbreaker | Fly Screen | Bird Wire | Safety Gratingı | 24 volt | Pneumatic | 7/24 |
| 1000 x 1000 | 2500 x 3000 | Std. | Ops. | Ops. | Ops. | Std. | Ops. | Std. |